Quiznetik

DC Generators | Set 2

1. A series generator can self-excite

Correct : B. only if the load current is not zero

2. A shunt generator can self-excite

Correct : A. only if the resistance of the field circuit is less than critical value

3. The terminal voltage of a series generator is 150 V when the load current is 5 A. If the load current is increased to 10 A, the terminal voltage will be

Correct : C. greater than 150 V

4. The open circuit voltage of a compound generator is 250 V. At full load the terminal voltage

Correct : C. may be greater or less than 250 V

5. Two D.C. shunt generators, each with armature resistance of 0.02 ohm and field resistance of 50 ohm run in parallel and supply a total current of 1000 amperes to the load circuit. If their e.m.fs. are 270 V and 265 V, their bus bar voltage will be

Correct : B. 267.5 V

6. The essential condition for parallel operation of two D.C. generators is that they have

Correct : C. the same drooping voltage charac-teristics

7. When two D.C. generators are running in parallel an equilizer bar is used

Correct : D. so that the two identical machines will pass approximately equal currents to the load

8. With a D.C. generator which of the following regulation is preferred ?

Correct : D. 1% regulation

9. Which generator would you prefer for feeding long D.C. transmission lines ?

Correct : C. Over compound generator

10. In a D.C. generator the critical resistance can be increased by

Correct : C. increasing its speed

11. The number of armature parallel paths in a two-pole D.C. generator having duplex lap winding is

Correct : B. 4

12. For both lap and wave windings, there are as many commutator bars as the number of

Correct : C. winding elements

13. The series field of a short-shunt D.C. generator is excited by

Correct : D. load current

14. As a result of armature reaction, the reduction in the total mutual air gap flux in a D.C. generator is approximately

Correct : D. 5 percent

15. Shunt generators are most suited for stable parallel operation because of their

Correct : C. drooping voltage characteristics

16. The main factor which leads to unstable parallel operation of flat and over compounded generators is

Correct : A. their rising voltage characteristics

17. If a self excited D.C. generator after being installed, fails to build up on its first trial run, the first thing to do is to

Correct : A. reverse the field connections

18. The insulating material for a cable should have

Correct : D. all of the above

19. Which of the following protects a cable against mechanical injury ?

Correct : C. Armouring

20. Which of the following insulation is used in cables ?

Correct : D. Any of the above

21. Empire tape is

Correct : A. varnished cambric

22. The thickness of the layer of insulation on the conductor, in cables, depends upon

Correct : C. voltage

23. The bedding on a cable consists of

Correct : C. any of the above

24. The insulating material for cables should

Correct : D. have all above properties

25. In a cable immediately above metallic sheath _____ is provided.

Correct : B. bedding

26. The current carrying capacity of cables in D.C. is more thanthat in A.C. mainly due to

Correct : C. smaller dielectric loss

27. In case of three core flexible cable the colour of the neutral is

Correct : A. blue

28. cables are used for 132 kV lines.

Correct : D. Extra super voltage

29. Conduit pipes are normally used to protect _____ cables.

Correct : A. unsheathed cables

30. The minimum dielectric stress in a cable is at

Correct : D. lead sheath

31. In single core cables armouring is not done to

Correct : A. avoid excessive sheath losses

32. Dielectric strength of rubber is around

Correct : C. 30 kV/mm

33. Low tension cables are generally used upto

Correct : D. 1000 V

34. In a cable, the maximum stress under operating conditions is at

Correct : D. conductor surface

35. High tension cables are generally used upto

Correct : A. 11kV

36. The surge resistance of cable is

Correct : C. 50 ohms

37. PVC stands for

Correct : A. polyvinyl chloride

38. In the cables, the location of fault is usually found out by comparing

Correct : C. the capacitances of insulated conductors

39. In capacitance grading of cables we use a ______ dielectric.

Correct : A. composite

40. Pressure cables are generally not used beyond

Correct : C. 66 kV

41. The material for armouring on cable is usually

Correct : C. any of the above

42. Cables, generally used beyond 66 kV are

Correct : A. oil filled

43. The relative permittivity of rubber is

Correct : A. between 2 and 3

44. Solid type cables are considered unreliable beyond 66 kV because

Correct : D. there is a danger of breakdown of insulation due to the presence of voids

45. If the length of a cable is doubled, its capacitance

Correct : C. becomes double

46. In cables the charging current

Correct : B. leads the voltage by 90°

47. A certain cable has an insulation of relative permittivity 4. If the insulation is replaced by one of relative permittivity 2, the capacitance of the cable will become

Correct : A. one half

48. If a cable of homogeneous insulation has a maximum stress of 10 kV/mm, then the dielectric strength of insulation should be

Correct : B. 10 kV/mm

49. In the cables, sheaths are used to

Correct : A. prevent the moisture from entering the cable

50. The intersheaths in the cables are used to

Correct : C. provide proper stress distribution

51. The electrostatic stress in underground cables is

Correct : C. maximum at the conductor and minimum at the sheath

52. The breakdown of insulation of the cable can be avoided economically by the use of

Correct : C. both (a) and (b)

53. The insulation of the cable decreases with

Correct : A. the increase in length of the insulation

54. A cable carrying alternating current has

Correct : B. hysteresis and leakage losses only

55. In a cable the voltage stress is maximum at

Correct : D. core of the conductor

56. Capacitance grading of cable implies

Correct : A. use of dielectrics of different permeabilities

57. Underground cables are laid at sufficient depth

Correct : C. to minimise the effect of shocks and vibrations due to gassing vehicles, etc.

58. The advantage of cables over overhead transmission lines is

Correct : C. can be used in congested areas

59. The thickness of metallic shielding on cables is usually

Correct : A. 0.04 mm

60. Cables for 220 kV lines are invariably

Correct : C. compressed oil or compressed gas insulated

61. Is a cable is to be designed for use on 1000 kV, which insulation would you prefer ?

Correct : D. Compressed SFe gas

62. If a power cable and a communication cable are to run parallel the minimum distance between the two, to avoid interference, should be

Correct : C. 50 cm

63. Copper as conductor for cables is used as

Correct : A. annealed

64. The insulating material should have

Correct : D. all of the above

65. The advantage of oil filled cables is

Correct : D. all of the above

66. The disadvantage with paper as insulating material is

Correct : A. it is hygroscopic

67. The breakdown voltage of a cable depends on

Correct : D. all of the above

68. In capacitance grading a homogeneous dielectric is used.

Correct : B. No

69. In congested areas where excavation is expensive and inconvenient 'draw in system' of laying of underground cables is often adopted.

Correct : A. Yes

70. Natural rubber is obtained from milky sap of tropical trees.

Correct : A. Yes

71. Rubber is most commonly used insulation in cables.

Correct : A. Yes

72. Polyethylene has very poor dielectric and ageing properties.

Correct : B. No

73. The metallic sheath may be made of lead or lead alloy or of aluminium.

Correct : B. No